Type II Matting: What IIA, IIB and IIC Actually Test

November 9, 2026 6 min readInsulation & Standards

IIA, IIB and IIC are three separate ASTM D178 tests, not three grades. Ozone with no visible effect, flame with 12.7 mm of char after 30 seconds, oil with 4 % volume swell. Pick the letter from the exposure, not from the room name.

Type II matting turns up on a datasheet as a letter. IIA, IIB, IIC — sometimes two of them stacked together. Plenty of buyers read those letters as grades: better, better, best, and they order the last one. That is not what they are. Each letter is a separate test on a separate failure, and none of the three changes the class figure that decides whether the mat belongs in front of your switchgear at all.

So, the structure first. ASTM D178 sorts matting two ways. Class sets the working voltage and the thickness that goes with it — Class 0 at 3.2 mm up to Class 4 at 12.7 mm, the ladder that runs 1.0 kV to 36 kV. Type sets what the material has to survive on top of the electrical job. Type I is the default supply grade. Type II is the family carrying special properties, and the sub-letters split by property: IIA for ozone, IIB for flame, IIC for oil.

One mat can hold more than one letter. That is where "Type II" as a single phrase starts hiding things.

1. What Type I has already cleared

Before any letter, the baseline. The published figures for this material ask for tensile strength of at least 4.83 MPa (700 psi) and elongation at break of at least 250 %, on both types. Ageing is 70 ± 1 °C for 168 hours, and after it the tensile strength must stay at or above 50 % of where it started. Thickness tolerance runs ±0.8 to ±1.2 mm depending on class, width ±13 to 25 mm.

Water absorption is where the two types part company, and not in the direction people expect: Type I is limited to 1.5 %, Type II to 3 %. Twice as much water allowed, in the family that carries the extra properties.

Read that again, because it kills the "II is the upgraded I" story. The letters do not buy a better mat all round. They buy three specific behaviours, and the spec is willing to give up some absorption to get them.

2. IIA — ozone, and the test is "no visible effect"

The IIA criterion is short: no visible effect after ozone exposure. No percentage, no depth in millimetres. An inspector looks at the surface and finds nothing.

That sounds soft next to the other two, and it is worth understanding why the standard is written that way. Ozone attacks elastomers at the points where the material is under tension, and the failure shows up as surface cracking — small, then a network of them. Once that starts, the mat's surface is no longer the surface that was tested. You cannot measure a crack that has not happened; "no visible effect" is the honest way to state a pass.

Where ozone comes from: anything that arcs or corona-discharges, plus the artificial light and electrical equipment our own storage guidance already tells you to keep matting away from. A mat stored next to a motor, or laid under gear that sparks, is living in ozone.

If the answer is IIA, the default Type I supply does not carry that claim — the letter is the claim.

3. IIB — flame, measured in charred millimetres

IIB is the one with a number in it. Expose the material to flame for 30 seconds, then measure how far the damage travelled: the charred height must come to 12.7 mm or less. Half an inch.

Two things that number is not. It is not "fireproof" — nothing in this product family is, and a supplier who says so is selling you a word rather than a test. And it is not a rating for a burning building; it is a check that a mat exposed to a small flame source will not carry that flame across its surface.

Compare it with the flame requirement published for IEC-grade matting, which is stated as the material not igniting. Different structure, same intent: the two standards chose different ways to ask whether the sheet spreads fire. Neither of them says "fireproof".

The practical case for IIB is the mat that sits near a welding position, a cable jointing kit, or anywhere a hot work permit gets written.

4. IIC — oil, measured as swell

IIC is oil resistance, and the figure is volume swell: 4 % or less after immersion.

Volume is the operative word. A mat can look untouched after a spill and still be 6 % bigger than it was, because the fluid went in rather than sat on top. Swell matters for two reasons. It changes the thickness that the class was calculated around, and it changes how the sheet behaves underfoot — a swollen mat creeps and lifts at the edges.

So do not judge oil exposure by wiping the surface. Either the compound carries IIC, or the exposure is a bet.

Where it comes up: hydraulic fluid around press and valve gear, transformer oil near a drain point, cutting fluid on a machine shop floor. If the floor sees any of it regularly, IIC is not an upgrade — it is the property the selection turns on.

5. Picking the letter from the exposure, not the room name

This is the part where a datasheet cannot help you, because the answer depends on your building.

The rule that does hold: the letter follows the exposure, and the class follows the voltage. They are independent questions, answered in that order. Fix the class from the maximum service voltage of the installation. Then ask what the floor actually sees.

  • Oil, hydraulic fluid or transformer oil on the floor — IIC, and if the same floor also sees solvent, say so, because the swell figure is tied to the fluid it was tested in.
  • Arcing or corona equipment, a motor, or a store room lit by discharge lamps — IIA.
  • A hot work position, a welding bay, anywhere a spark could land on the sheet — IIB.
  • More than one of those — quote the letters you need, together. A mat can be IIA/IIB, or all three, and the datasheet has to name them explicitly.

What does not work is treating the room name as the specification. "Switchroom" and "substation" tell you nothing about whether the failure you face is ozone, flame or oil. The voltage tells you the class. The floor tells you the letters.

6. What to put on the enquiry

Four lines, and the fourth is the one people leave out:

  1. 1The standard — IEC 61111 or ASTM D178 — because the two sort matting differently and the thickness ladder is not the same.
  2. 2The class, taken from the installation's maximum service voltage.
  3. 3The type letters required, spelled out: IIA, IIB, IIC, or the combination.
  4. 4The evidence you will accept: a type test report that names the letter, not a line in a brochure.

Our matting is manufactured to IEC 61111 and ASTM D178, and the type letters are quoted against the material we would actually ship — so tell us the exposure and the class, and we will come back with the letters we can put our name to, plus the report behind them.

If you are choosing between the two standards on the same job, the thickness and voltage reference is here: Insulating Mat Thickness and Voltage Reference. And if the mat is already bought and sitting in a store, the storage range matters more than the letters: Mat Storage vs In-Service Temperature.

Write to [email protected] with the class, the letters and the fluid or flame source you are protecting against. We will confirm the type against the material and send the test report for it.

Need this confirmed against your own installation?

Send us the network voltage, the standard you are specifying against and the ambient conditions. Our engineers will confirm the class, thickness and test report, and reply with lead time.

Ask a technical question
Start Your Project

Let's build your power infrastructure together

Send us your specifications — insulating mats, gloves, voltage detectors, grounding systems or safety tooling projects. Our engineers respond within 24 hours with technical recommendations and pricing.