Mat Storage vs In-Service Temperature: Why the Two Ranges Differ

November 2, 2026 6 min readInsulation & Standards

One manufacturer's IEC 61111 matting is published at −40 °C to +55 °C working and +10 °C to +21 °C in storage. Two ranges, two different jobs — and the storage one is the one nobody reads.

Insulating matting gets published with two temperature ranges, and they sit a long way apart. One manufacturer's instructions for IEC 61111 matting give a working range of −40 °C to +55 °C, and a storage range of +10 °C to +21 °C. Another gives −25 °C to +55 °C for working.

Read those as roughly the same thing and the storeroom quietly becomes the weak point in the system. They are not the same thing. They do not even describe the same kind of failure.

1. Two numbers, two questions

The working range answers one question: what temperatures can this mat sit in while it is doing its job — laid in front of a switchgear panel, bolted to a floor, walked on in a cold substation in February?

The storage range answers a different one: what conditions keep the material from changing while it waits.

The first is about the material staying usable under load. The second is about the material not ageing. A mat can meet the first and fail the second, which is exactly why the second number is tighter.

2. What the published ranges actually are

Straight from the published instructions, without tidying them up:

SourceWorkingStorage
Manufacturer A (CATU)−40 °C to +55 °C+10 °C to +21 °C
Manufacturer B (Duratuf)−25 °C to +55 °Cnot stated in the same table

Two things worth noticing. The top of the working range agrees — +55 °C both times. The bottom does not: −40 against −25.

That disagreement is the tell. These figures are product data from two manufacturers, not a single clause of the standard that everyone copies. So do not build a specification on "the standard says −40". Ask the supplier of the mat you are actually buying, and get the answer for that product.

The storage range, where it is published, is the short one: +10 °C to +21 °C. That is a store room, not a warehouse.

3. Why storage is the narrower range

A mat in service has a job that forces some tolerance. It sits on a floor, it gets walked on, it is expected to work in whatever the building does. Its rating is defined around that.

A mat in storage has no such excuse. Nothing is asking it to perform, so nothing justifies letting it sit outside the conditions where the compound stays as it was mixed and cured. Over months, heat accelerates the changes that harden and embrittle an elastomer, and a cool, stable store slows them down. That is the whole logic of the tighter number.

Which is why the storage range is best read as a maintenance instruction rather than a survivable limit. Exceed the working range and the mat may fail while somebody is standing on it. Exceed the storage range and nothing happens today — it just quietly stops being the mat that was tested.

4. What actually damages a mat in the store

Temperature is only one line of it. The same guidance rules out four more things, and all four are common in real storerooms:

  • Compression and folding. Mats get folded to save shelf space. Folded is exactly what the instructions say not to do.
  • Heat sources. A radiator, a warm wall, a drying oven in the same room.
  • Direct sunlight. Not "some daylight" — direct sun, on a black rubber sheet, in a room with a roof light.
  • Ozone and artificial light. The two that nobody thinks about, and both are named.

Then add the ordinary one: temperature cycling. A store that swings warm by day and cold at night condenses water on the coldest surface in the room, and a rubber sheet on a concrete floor is usually the coldest thing there. Nothing feels damp. The material still sees it.

5. The properties the range is protecting

This is where the storage question stops being housekeeping. The mechanical figures published for IEC 61111 matting are retention figures, not just starting values:

  • Puncture resistance at least 70 N, slip resistance at least 50 N
  • After heat ageing at 70 ± 2 °C for 168 hours, puncture resistance must stay at or above 80 % of its original value
  • After acid or oil exposure, mechanical values must stay at or above 75 % of the original
  • At −25 ± 3 °C there must be no visible tearing or cracking
  • Flame: the material must not ignite

Read the first two together. The standard's own ageing test is a week at 70 °C — and the pass mark is that the material keeps 80 % of its puncture resistance. A store room that runs hot for two years is doing a slower version of that test, with nobody recording the result.

That is how a mat ends up factory-new in appearance and past its useful life in fact. It still looks like a mat. It no longer has the margin the rating assumed.

And the clock is separate from all of it: matting that has been in storage for 12 months has to be examined and electrically tested before it goes into service, whether or not anyone has stood on it. Class 0 is a visual examination; Class 1 to 4 go through a one-minute dielectric test at 10, 20, 30 or 40 kV depending on class. Age alone triggers it.

6. What to write into the store procedure

Five lines, and they fit on one page:

  1. 1Store temperature: the range the manufacturer publishes for the product you buy — not a general figure off a chart. Where it is published as +10 °C to +21 °C, that is the number to hold the room to.
  2. 2No folding, no compression. Rolled or laid flat, on a rack, not on the floor.
  3. 3Away from heat, direct sun, artificial light and ozone. Which in practice means: not against an external wall, not under a roof light, not next to a motor or a welder.
  4. 4Record two dates: received, and first issued. The 12-month storage test runs from the first.
  5. 5Log the room. One thermometer and one humidity reading a week beats an argument in year three.

None of that needs new equipment. It needs the storage range to be treated as a specification instead of small print — which is the one thing the working range never had a problem with.

If you are writing a store and handling procedure for matting and want the published temperature range, the retention figures and the retest interval confirmed for the product you are specifying, write to [email protected].