The 2018 revision moved insulating footwear from two classes to six, but the DC ladder still stops at Class 2. The class table, the antistatic boundary, and the lines that belong on the order.
Most insulating footwear specifications in circulation were written against the 1999 edition, and the 1999 edition only had two classes. That is the first thing worth knowing, because it means a boot quoted as “EN 50321 Class 0” today is being compared against a ladder that no longer exists in that form.
EN 50321 was replaced by EN 50321-1:2018, approved by CENELEC on 14 September 2017. The revision added AC classes 1, 2, 3 and 4 — the 1999 edition went no further than Class 0. If you are comparing a 2005 certificate against a 2024 quotation, you are comparing two different scales.
1. The class ladder, and where it stops
Straight from clause 4.1, by the nominal voltage of the installation:
| Class | Maximum nominal voltage |
|---|---|
| Class 00 | 500 V AC / 750 V DC |
| Class 0 | 1 000 V AC / 1 500 V DC |
| Class 1 | 7 500 V AC / 11 250 V DC |
| Class 2 | 17 000 V AC / 25 500 V DC |
| Class 3 | 26 500 V AC |
| Class 4 | 36 000 V AC |
Two things in that table decide most purchase orders.
The DC column stops at Class 2. Classes 3 and 4 carry an AC figure only. The 2018 foreword says the same thing in its own words: DC voltage testing was added for class 00, 0, 1 and 2 — not for 3 and 4. So a 25 kV DC traction installation and a 25 kV AC distribution installation do not take the same boot, and no Class 4 boot is rated for DC at all, even though its AC ceiling is 36 kV.
The ceiling is 36 kV AC. That is the top of the standard's scope, stated in clause 1. Above it, insulating footwear is not the protection layer — the mat and the clearance are. A supplier offering “EN 50321-1 Class 5” has invented a class.
2. Antistatic is not electrical protection
This is the line in the standard most often ignored, and it is explicit in clause 1: antistatic, electrical shock resistant and conductive footwear are not covered by EN 50321-1. Parts 2 and 3, for shock-resistant and conductive footwear, are still in development.
The reason is arithmetic. The standard's own definitions give the resistance ranges:
- Antistatic footwear: above 100 kΩ and not more than 1 000 MΩ
- Conductive footwear for live working: 0 to 10 kΩ
Those two windows do not overlap, and they are asking for opposite things. Antistatic footwear is designed to bleed static away slowly so it does not accumulate; insulating footwear is designed to not conduct at all. A requisition line reading “insulating boots, antistatic” is asking a supplier to satisfy two standards at once, and it usually resolves into whichever one the factory happens to test.
If the site genuinely needs static control — a solvent area, a powder handling area — that is a different boot and a different problem from electrical insulation. Say which one the job is, and buy that one.
3. The electrical standard does not replace the safety standard
An insulating boot is still a boot. Clause 4.2.1 requires electrical insulating footwear to comply with EN ISO 20345:2011 Table 2 Class II, or EN ISO 20346:2014 Table 2, or EN ISO 20347:2012 Table 2, with any additional requirements taken from the relevant Table 18 (Table 16 in 20347). Overboots must comply with EN ISO 20347:2012 Table 2, and the closing system must stay secure once closed.
So a complete footwear specification names two things: the electrical class, and the mechanical standard it sits on top of. A quotation that names only the electrical class is half a specification.
4. Shape matters more than people expect
Clause 4.2.2.1 defines four footwear designs: A low shoe, B ankle boot, C half-knee boot, D knee-height boot. Overboots follow Figure 2 and must at least cover the height of the footwear worn underneath — which sounds obvious until someone buys short overboots to go over tall boots.
For Class 00 and Class 0 in design A, the height of the upper has to be at least 75 mm. Table 1 then sets a minimum height to be tested by shoe size and design — at sizes 43–44, a design D boot is tested at 116 mm of upper. The practical reading: the taller the boot, the more of it the electrical test actually covers, and the class figure only means something about the part that was tested.
5. Marking and the seven lines that belong on the order
Annex B makes the live-working marking the double triangle, symbol IEC 60417-5216:2002-10. The class is marked alongside it. When the crate arrives, the class on the boot is the claim; the certificate is what backs it.
For the requisition, these lines are the ones that hold up:
- 1Standard and edition — EN 50321-1:2018, not “EN 50321”
- 2Electrical class, with AC or DC named
- 3The installation voltage the class was derived from
- 4Mechanical standard (EN ISO 20345 Class II, or 20346, or 20347)
- 5Design (A/B/C/D) and size range
- 6Test report — type test for the model, and the routine test record per pair
- 7Whether the application needs static control, which is a separate purchase
Line 2 is where DC installations go wrong, because “Phase 2 is 25 kV” reads as Class 2 territory in AC and as Class 2 territory in DC, but only one of those boots has a DC rating at that level.
6. Storage and inspection
Annex A covers storage, examination before use, and precautions during and after use, and A.2 addresses periodic inspection. It is informative rather than prescriptive on interval — the survey interval comes from your own procedure. What the standard does fix is that the boot has to be examined before use, which for a rubber boot means looking at the sole, the flex points and the inside of the shaft, not just the outer surface.
7. What we supply
Our 35 kV insulated rubber boots are built for power transmission construction: natural rubber, dielectric-tested, in red, green or black, MOQ 5 pairs. If your specification is written against EN 50321-1:2018, tell us the class and whether the installation is AC or DC — the two answers lead to different boots, and for DC above 25.5 kV they lead to a different protection strategy altogether.
The glove class ladder follows a parallel logic and is worth reading alongside this one, because a glove and a boot on the same job are frequently specified to different classes for good reasons.
Need this confirmed against your own installation?
Send us the network voltage, the standard you are specifying against and the ambient conditions. Our engineers will confirm the class, thickness and test report, and reply with lead time.
Ask a technical question